31
UNDERGROUND FAULT INDICATORS
GFD
Ground Fault Detector
Key Features
Detects ground faults by sensing the vector sum of the current
flowing through a three-conductor cable.
Choice of three reset options (secondary voltage, load current, or
time) to meet various application needs.
Install the split-core sensor on three-phase cables without opening
the primary.
Large reflective red target is easy to see both at night and during
the day.
Submersible vinyl-coated sensing core.
Stainless-steel hardware and UV-stabilized materials ensure long
product life.
Thousands of SEL GFDs in service today help customers around the
world quickly locate ground faults.
Specifications
Power Source Secondary voltage (120 to 240 Vac
L- N
at
50 to 60 Hz); load current (3 A); or
lithium battery for timed reset products
Reset Time (timed reset
models only)
2, 4, or 8 hours
Nominal Trip Ratings 20, 40, 50, or 100 A
Trip Tolerance
±10%
Maximum Fault Current 25 kA for 10 cycles
Trip Response Time 1 ms
Outer Diameter
Clamping Range
4" (6" optional)
Housing Materials UV-stabilized polycarbonate resin
Submersibility Up to 15 feet
Temperature Range —40° to +85°C
Reliable ground fault detection
for three-conductor cable
applications.
A Ground Fault Detector (Model GFD50SA) provides fault indication in
the Middle East.