Tel: +1.847.362.8304 | Fax: +1.847.362.8396 | www.eosmfg.com
E. O. SCHWEITZER MANUFACTURING, A DIVISION OF SEL
31
UNDERGROUND FAULT INDICATORS
GFD
—
Ground Fault Detector
Key Features
• Detects ground faults by sensing the vector sum of the current
flowing through a three-conductor cable.
• Choice of three reset options (secondary voltage, load current, or
time) to meet various application needs.
• Install the split-core sensor on three-phase cables without opening
the primary.
• Large reflective red target is easy to see both at night and during
the day.
• Submersible vinyl-coated sensing core.
• Stainless-steel hardware and UV-stabilized materials ensure long
product life.
• Thousands of SEL GFDs in service today help customers around the
world quickly locate ground faults.
Specifications
Power Source Secondary voltage (120 to 240 Vac
L- N
at
50 to 60 Hz); load current (≥3 A); or
lithium battery for timed reset products
Reset Time (timed reset
models only)
2, 4, or 8 hours
Nominal Trip Ratings 20, 40, 50, or 100 A
Trip Tolerance
±10%
Maximum Fault Current 25 kA for 10 cycles
Trip Response Time 1 ms
Outer Diameter
Clamping Range
4" (6" optional)
Housing Materials UV-stabilized polycarbonate resin
Submersibility Up to 15 feet
Temperature Range —40° to +85°C
Reliable ground fault detection
for three-conductor cable
applications.
A Ground Fault Detector (Model GFD50SA) provides fault indication in
the Middle East.